--- /dev/null Thu Jan 01 00:00:00 1970 +0000
+++ b/bacnet/runtime/msi.c Mon Jun 11 08:34:15 2018 +0200
@@ -0,0 +1,556 @@
+/**************************************************************************
+*
+* Copyright (C) 2012 Steve Karg <skarg@users.sourceforge.net>
+* Copyright (C) 2017 Mario de Sousa <msousa@fe.up.pt>
+*
+* Permission is hereby granted, free of charge, to any person obtaining
+* a copy of this software and associated documentation files (the
+* "Software"), to deal in the Software without restriction, including
+* without limitation the rights to use, copy, modify, merge, publish,
+* distribute, sublicense, and/or sell copies of the Software, and to
+* permit persons to whom the Software is furnished to do so, subject to
+* the following conditions:
+*
+* The above copyright notice and this permission notice shall be included
+* in all copies or substantial portions of the Software.
+*
+* THE SOFTWARE IS PROVIDED "AS IS", WITHOUT WARRANTY OF ANY KIND,
+* EXPRESS OR IMPLIED, INCLUDING BUT NOT LIMITED TO THE WARRANTIES OF
+* MERCHANTABILITY, FITNESS FOR A PARTICULAR PURPOSE AND NONINFRINGEMENT.
+* IN NO EVENT SHALL THE AUTHORS OR COPYRIGHT HOLDERS BE LIABLE FOR ANY
+* CLAIM, DAMAGES OR OTHER LIABILITY, WHETHER IN AN ACTION OF CONTRACT,
+* TORT OR OTHERWISE, ARISING FROM, OUT OF OR IN CONNECTION WITH THE
+* SOFTWARE OR THE USE OR OTHER DEALINGS IN THE SOFTWARE.
+*
+*********************************************************************/
+
+/* Multi-state Input Objects */
+
+#include <stdbool.h>
+#include <stdint.h>
+#include <stdio.h>
+
+#include "config_bacnet_for_beremiz_%(locstr)s.h" /* the custom configuration for beremiz pluginh */
+#include "bacdef.h"
+#include "bacdcode.h"
+#include "bacenum.h"
+#include "bacapp.h"
+#include "rp.h"
+#include "wp.h"
+#include "msi_%(locstr)s.h"
+#include "handlers.h"
+
+
+/* initial value for present_value property of each object */
+#define MSI_VALUE_INIT (1)
+
+/* The IEC 61131-3 located variables mapped onto the Multi-state Input objects of BACnet protocol */
+%(MSI_lvars)s
+
+
+/* The array where we keep all the state related to the Multi-state Input Objects */
+#define MAX_MULTISTATE_INPUTS %(MSI_count)s
+static MULTISTATE_INPUT_DESCR MSI_Descr[MAX_MULTISTATE_INPUTS] = {
+%(MSI_param)s
+};
+
+
+
+/* These three arrays are used by the ReadPropertyMultiple handler,
+ * as well as to initialize the XXX_Property_List used by the
+ * Property List (PROP_PROPERTY_LIST) property.
+ */
+static const int Multistate_Input_Properties_Required[] = {
+ /* (1) Currently Supported */
+ /* (2) Required by standard ASHRAE 135-2016 */
+ /*(1)(2) */
+ PROP_OBJECT_IDENTIFIER, /* R R ( 75) */
+ PROP_OBJECT_NAME, /* R R ( 77) */
+ PROP_OBJECT_TYPE, /* R R ( 79) */
+ PROP_PRESENT_VALUE, /* W R ( 85) */
+ PROP_STATUS_FLAGS, /* R R (111) */
+ PROP_EVENT_STATE, /* R R ( 36) */
+ PROP_OUT_OF_SERVICE, /* W R ( 81) */
+ PROP_NUMBER_OF_STATES, /* R R ( 74) */
+// PROP_PROPERTY_LIST, /* R R (371) */
+ -1
+};
+
+static const int Multistate_Input_Properties_Optional[] = {
+ /* (1) Currently Supported */
+ /* (2) Required by standard ASHRAE 135-2016 */
+ /*(1)(2) */
+ PROP_DESCRIPTION, /* R O ( 28) */
+ PROP_STATE_TEXT, /* R O (110) */
+ -1
+};
+
+static const int Multistate_Input_Properties_Proprietary[] = {
+ -1
+};
+
+
+/* This array stores the PROPERTY_LIST which may be read by clients.
+ * End of list is marked by following the last element with the value '-1'
+ *
+ * It is initialized by Multistate_Input_Init() based off the values
+ * stored in Multistate_Input_Properties_Required
+ * Multistate_Input_Properties_Optional
+ * Multistate_Input_Properties_Proprietary
+ */
+/* TODO: Allocate memory for this array with malloc() at startup */
+static int Multistate_Input_Properties_List[64];
+
+
+
+
+
+/********************************************************/
+/** Callback functions. **/
+/** Functions required by BACnet devie implementation. **/
+/********************************************************/
+
+
+/* This is a callback function. Callback set in My_Object_Table[] array declared in device.c, */
+void Multistate_Input_Property_Lists(
+ const int **pRequired,
+ const int **pOptional,
+ const int **pProprietary)
+{
+ if (pRequired)
+ *pRequired = Multistate_Input_Properties_Required;
+ if (pOptional)
+ *pOptional = Multistate_Input_Properties_Optional;
+ if (pProprietary)
+ *pProprietary = Multistate_Input_Properties_Proprietary;
+
+ return;
+}
+
+
+
+/* This is a callback function. Callback set in My_Object_Table[] array declared in device.c, */
+void Multistate_Input_Init(
+ void)
+{
+ unsigned int i, j;
+
+ /* initialize the Multistate_Input_Properties_List array */
+ int len = 0;
+ len += BACnet_Init_Properties_List(Multistate_Input_Properties_List + len,
+ Multistate_Input_Properties_Required);
+ len += BACnet_Init_Properties_List(Multistate_Input_Properties_List + len,
+ Multistate_Input_Properties_Optional);
+ len += BACnet_Init_Properties_List(Multistate_Input_Properties_List + len,
+ Multistate_Input_Properties_Proprietary);
+
+ /* initialize all the analog output priority arrays to NULL */
+ for (i = 0; i < MAX_MULTISTATE_INPUTS; i++) {
+ MSI_Descr[i].Present_Value = MSI_VALUE_INIT;
+ for (j = 0; j < MSI_Descr[i].Number_Of_States; j++) {
+ sprintf(MSI_Descr[i].State_Text[j], "State %%d", j+1);
+ }
+ }
+ return;
+}
+
+
+
+/* validate that the given instance exists */
+/* This is a callback function. Callback set in My_Object_Table[] array declared in device.c, */
+bool Multistate_Input_Valid_Instance(
+ uint32_t object_instance)
+{
+ // fprintf(stderr, "BACnet plugin: Multistate_Input_Valid_Instance(obj_ID=%%u) called!\n", object _instance);
+ return (Multistate_Input_Instance_To_Index(object_instance) < MAX_MULTISTATE_INPUTS);
+}
+
+
+/* the number of Multistate Value Objects */
+/* This is a callback function. Callback set in My_Object_Table[] array declared in device.c, */
+unsigned Multistate_Input_Count(void) {return MAX_MULTISTATE_INPUTS;}
+
+
+/* returns the instance (i.e. Object Identifier) that correlates to the correct index */
+/* This is a callback function. Callback set in My_Object_Table[] array declared in device.c, */
+uint32_t Multistate_Input_Index_To_Instance(unsigned index) {return MSI_Descr[index].Object_Identifier;}
+
+
+
+
+
+
+/* returns the index that correlates to the correct instance number (Object Identifier) */
+unsigned Multistate_Input_Instance_To_Index(
+ uint32_t object_instance)
+{
+ unsigned index = 0;
+
+ for (index = 0; index < MAX_MULTISTATE_INPUTS; index++)
+ if (object_instance == MSI_Descr[index].Object_Identifier)
+ return index;
+
+ /* error, this object ID is not in our list! */
+ return MAX_MULTISTATE_INPUTS;
+}
+
+
+
+
+
+uint32_t Multistate_Input_Present_Value(
+ uint32_t object_instance)
+{
+ uint32_t value = MSI_VALUE_INIT;
+ unsigned index = 0; /* offset from instance lookup */
+
+ index = Multistate_Input_Instance_To_Index(object_instance);
+ if (index < MAX_MULTISTATE_INPUTS)
+ value = MSI_Descr[index].Present_Value;
+
+ return value;
+}
+
+
+
+bool Multistate_Input_Present_Value_Set(
+ uint32_t object_instance,
+ uint32_t value)
+{
+ unsigned index = 0; /* offset from instance lookup */
+
+ index = Multistate_Input_Instance_To_Index(object_instance);
+ if (index >= MAX_MULTISTATE_INPUTS)
+ return false;
+
+ if ((value == 0) || (value > MSI_Descr[index].Number_Of_States))
+ return false;
+
+ MSI_Descr[index].Present_Value = (uint8_t) value;
+ return true;
+}
+
+
+
+
+bool Multistate_Input_Out_Of_Service(
+ uint32_t object_instance)
+{
+ bool value = false;
+ unsigned index = 0;
+
+ index = Multistate_Input_Instance_To_Index(object_instance);
+ if (index < MAX_MULTISTATE_INPUTS) {
+ value = MSI_Descr[index].Out_Of_Service;
+ }
+
+ return value;
+}
+
+
+
+void Multistate_Input_Out_Of_Service_Set(
+ uint32_t object_instance,
+ bool value)
+{
+ unsigned index = 0;
+
+ index = Multistate_Input_Instance_To_Index(object_instance);
+ if (index < MAX_MULTISTATE_INPUTS) {
+ MSI_Descr[index].Out_Of_Service = value;
+ }
+
+ return;
+}
+
+
+
+static char *Multistate_Input_Description(
+ uint32_t object_instance)
+{
+ unsigned index = 0; /* offset from instance lookup */
+ char *pName = NULL; /* return value */
+
+ index = Multistate_Input_Instance_To_Index(object_instance);
+ if (index < MAX_MULTISTATE_INPUTS) {
+ pName = MSI_Descr[index].Description;
+ }
+
+ return pName;
+}
+
+
+
+/* This is a callback function. Callback set in My_Object_Table[] array declared in device.c, */
+bool Multistate_Input_Object_Name(
+ uint32_t object_instance,
+ BACNET_CHARACTER_STRING * object_name)
+{
+ unsigned index = 0; /* offset from instance lookup */
+ bool status = false;
+
+ index = Multistate_Input_Instance_To_Index(object_instance);
+ if (index < MAX_MULTISTATE_INPUTS) {
+ status = characterstring_init_ansi(object_name, MSI_Descr[index].Object_Name);
+ }
+
+ return status;
+}
+
+
+
+/* return apdu len, or BACNET_STATUS_ERROR on error */
+/* This is a callback function. Callback set in My_Object_Table[] array declared in device.c, */
+int Multistate_Input_Read_Property(
+ BACNET_READ_PROPERTY_DATA * rpdata)
+{
+ int len = 0;
+ int apdu_len = 0; /* return value */
+ BACNET_BIT_STRING bit_string;
+ BACNET_CHARACTER_STRING char_string;
+ uint32_t present_value = 0;
+ unsigned object_index = 0;
+ unsigned i = 0;
+ bool state = false;
+ uint8_t *apdu = NULL;
+
+ if ((rpdata == NULL) || (rpdata->application_data == NULL) ||
+ (rpdata->application_data_len == 0)) {
+ return 0;
+ }
+
+ object_index = Multistate_Input_Instance_To_Index(rpdata->object_instance);
+ if (object_index >= MAX_MULTISTATE_INPUTS) {
+ rpdata->error_class = ERROR_CLASS_OBJECT;
+ rpdata->error_code = ERROR_CODE_UNKNOWN_OBJECT;
+ return BACNET_STATUS_ERROR;
+ }
+
+ apdu = rpdata->application_data;
+ switch (rpdata->object_property) {
+ case PROP_OBJECT_IDENTIFIER:
+ apdu_len =
+ encode_application_object_id(&apdu[0],
+ OBJECT_MULTI_STATE_INPUT, rpdata->object_instance);
+ break;
+ case PROP_OBJECT_NAME:
+ Multistate_Input_Object_Name(rpdata->object_instance,
+ &char_string);
+ apdu_len =
+ encode_application_character_string(&apdu[0], &char_string);
+ break;
+ case PROP_DESCRIPTION:
+ characterstring_init_ansi(&char_string,
+ Multistate_Input_Description(rpdata->object_instance));
+ apdu_len =
+ encode_application_character_string(&apdu[0], &char_string);
+ break;
+ case PROP_OBJECT_TYPE:
+ apdu_len =
+ encode_application_enumerated(&apdu[0],
+ OBJECT_MULTI_STATE_INPUT);
+ break;
+ case PROP_PRESENT_VALUE:
+ present_value =
+ Multistate_Input_Present_Value(rpdata->object_instance);
+ apdu_len = encode_application_unsigned(&apdu[0], present_value);
+ break;
+ case PROP_STATUS_FLAGS:
+ /* note: see the details in the standard on how to use these */
+ bitstring_init(&bit_string);
+ bitstring_set_bit(&bit_string, STATUS_FLAG_IN_ALARM, false);
+ bitstring_set_bit(&bit_string, STATUS_FLAG_FAULT, false);
+ bitstring_set_bit(&bit_string, STATUS_FLAG_OVERRIDDEN, false);
+ if (Multistate_Input_Out_Of_Service(rpdata->object_instance)) {
+ bitstring_set_bit(&bit_string, STATUS_FLAG_OUT_OF_SERVICE,
+ true);
+ } else {
+ bitstring_set_bit(&bit_string, STATUS_FLAG_OUT_OF_SERVICE,
+ false);
+ }
+ apdu_len = encode_application_bitstring(&apdu[0], &bit_string);
+ break;
+ case PROP_EVENT_STATE:
+ /* note: see the details in the standard on how to use this */
+ apdu_len =
+ encode_application_enumerated(&apdu[0], EVENT_STATE_NORMAL);
+ break;
+ case PROP_OUT_OF_SERVICE:
+ state = MSI_Descr[object_index].Out_Of_Service;
+ apdu_len = encode_application_boolean(&apdu[0], state);
+ break;
+ case PROP_NUMBER_OF_STATES:
+ apdu_len =
+ encode_application_unsigned(&apdu[apdu_len],
+ MSI_Descr[object_index].Number_Of_States);
+ break;
+ case PROP_STATE_TEXT:
+ BACnet_encode_array(MSI_Descr[object_index].State_Text,
+ MSI_Descr[object_index].Number_Of_States,
+ retfalse, BACnet_encode_character_string);
+ break;
+// case PROP_PROPERTY_LIST:
+// BACnet_encode_array(Multistate_Input_Properties_List,
+// property_list_count(Multistate_Input_Properties_List),
+// retfalse, encode_application_enumerated);
+// break;
+ default:
+ rpdata->error_class = ERROR_CLASS_PROPERTY;
+ rpdata->error_code = ERROR_CODE_UNKNOWN_PROPERTY;
+ apdu_len = BACNET_STATUS_ERROR;
+ break;
+ }
+ /* only array properties can have array options */
+ if ((apdu_len >= 0) && (rpdata->object_property != PROP_STATE_TEXT) &&
+// (rpdata->object_property != PROP_PROPERTY_LIST) &&
+ (rpdata->array_index != BACNET_ARRAY_ALL)) {
+ rpdata->error_class = ERROR_CLASS_PROPERTY;
+ rpdata->error_code = ERROR_CODE_PROPERTY_IS_NOT_AN_ARRAY;
+ apdu_len = BACNET_STATUS_ERROR;
+ }
+
+ return apdu_len;
+}
+
+/* returns true if successful */
+/* This is a callback function. Callback set in My_Object_Table[] array declared in device.c, */
+bool Multistate_Input_Write_Property(
+ BACNET_WRITE_PROPERTY_DATA * wp_data)
+{
+ bool status = false; /* return value */
+ int len = 0;
+ unsigned object_index = 0;
+ BACNET_APPLICATION_DATA_VALUE value;
+
+ /* decode the some of the request */
+ len =
+ bacapp_decode_application_data(wp_data->application_data,
+ wp_data->application_data_len, &value);
+ /* FIXME: len < application_data_len: more data? */
+ if (len < 0) {
+ /* error while decoding - a value larger than we can handle */
+ wp_data->error_class = ERROR_CLASS_PROPERTY;
+ wp_data->error_code = ERROR_CODE_VALUE_OUT_OF_RANGE;
+ return false;
+ }
+ if ((wp_data->object_property != PROP_STATE_TEXT) &&
+ (wp_data->array_index != BACNET_ARRAY_ALL)) {
+ /* only array properties can have array options */
+ wp_data->error_class = ERROR_CLASS_PROPERTY;
+ wp_data->error_code = ERROR_CODE_PROPERTY_IS_NOT_AN_ARRAY;
+ return false;
+ }
+ /* No need to check whether object_index is within bounds.
+ * Has already been checked before Multistate_Input_Write_Property() is called
+ */
+ object_index = Multistate_Input_Instance_To_Index(wp_data->object_instance);
+
+ switch (wp_data->object_property) {
+ case PROP_PRESENT_VALUE:
+ status =
+ WPValidateArgType(&value, BACNET_APPLICATION_TAG_UNSIGNED_INT,
+ &wp_data->error_class, &wp_data->error_code);
+ if (!status) {
+ wp_data->error_class = ERROR_CLASS_PROPERTY;
+ wp_data->error_code = ERROR_CODE_INVALID_DATA_TYPE;
+ status = false; // not really necessary here.
+ } else {
+ if (!MSI_Descr[object_index].Out_Of_Service) {
+ /* input objects can only be written to when Out_Of_Service is true! */
+ wp_data->error_class = ERROR_CLASS_PROPERTY;
+ wp_data->error_code = ERROR_CODE_WRITE_ACCESS_DENIED;
+ status = false;
+ } else {
+ status =
+ Multistate_Input_Present_Value_Set
+ (wp_data->object_instance, value.type.Unsigned_Int);
+ if (!status) {
+ wp_data->error_class = ERROR_CLASS_PROPERTY;
+ wp_data->error_code = ERROR_CODE_VALUE_OUT_OF_RANGE;
+ status = false; // not really necessary here.
+ }
+ }
+ }
+ break;
+ case PROP_OUT_OF_SERVICE:
+ {
+ bool Previous_Out_Of_Service = MSI_Descr[object_index].Out_Of_Service;
+ status =
+ WPValidateArgType(&value, BACNET_APPLICATION_TAG_BOOLEAN,
+ &wp_data->error_class, &wp_data->error_code);
+ if (status) {
+ MSI_Descr[object_index].Out_Of_Service = value.type.Boolean;
+ if (Previous_Out_Of_Service && !MSI_Descr[object_index].Out_Of_Service)
+ /* We have just changed from Out_of_Service -> In Service */
+ /* We need to update the Present_Value to the value
+ * currently in the PLC...
+ */
+ MSI_Descr[object_index].Present_Value =
+ *(MSI_Descr[object_index].Located_Var_ptr);
+ }
+ break;
+ }
+ case PROP_OBJECT_IDENTIFIER:
+ case PROP_OBJECT_NAME:
+ case PROP_OBJECT_TYPE:
+ case PROP_STATUS_FLAGS:
+ case PROP_EVENT_STATE:
+ case PROP_NUMBER_OF_STATES:
+ case PROP_DESCRIPTION:
+ case PROP_STATE_TEXT:
+// case PROP_PROPERTY_LIST:
+ wp_data->error_class = ERROR_CLASS_PROPERTY;
+ wp_data->error_code = ERROR_CODE_WRITE_ACCESS_DENIED;
+ break;
+ default:
+ wp_data->error_class = ERROR_CLASS_PROPERTY;
+ wp_data->error_code = ERROR_CODE_UNKNOWN_PROPERTY;
+ break;
+ }
+
+ return status;
+}
+
+
+
+
+
+/********************************************/
+/** Functions required for Beremiz plugin **/
+/********************************************/
+
+
+
+void Multistate_Input_Copy_Present_Value_to_Located_Var(void) {
+ unsigned i;
+ for (i = 0; i < MAX_MULTISTATE_INPUTS; i++) {
+ // decouple PLC's Located Variable from Bacnet Object's Present Value if Out_Of_Service is true
+ if (MSI_Descr[i].Out_Of_Service)
+ continue;
+
+ // copy the value
+ *(MSI_Descr[i].Located_Var_ptr) = Multistate_Input_Present_Value(MSI_Descr[i].Object_Identifier);
+ }
+}
+
+
+
+void Multistate_Input_Copy_Located_Var_to_Present_Value(void) {
+ unsigned i;
+ for (i = 0; i < MAX_MULTISTATE_INPUTS; i++) {
+ // decouple PLC's Located Variable from Bacnet Object's Present Value if Out_Of_Service is true
+ if (MSI_Descr[i].Out_Of_Service)
+ continue;
+
+ // Make sure local device does not set Present_Value to 0, nor higher than Number_Of_States
+ if ((*(MSI_Descr[i].Located_Var_ptr) > MSI_Descr[i].Number_Of_States) ||
+ (*(MSI_Descr[i].Located_Var_ptr) == 0))
+ continue;
+
+ // Everything seems to be OK. Copy the value