1 /************************************************************************** |
|
2 * |
|
3 * Copyright (C) 2012 Steve Karg <skarg@users.sourceforge.net> |
|
4 * Copyright (C) 2017 Mario de Sousa <msousa@fe.up.pt> |
|
5 * |
|
6 * Permission is hereby granted, free of charge, to any person obtaining |
|
7 * a copy of this software and associated documentation files (the |
|
8 * "Software"), to deal in the Software without restriction, including |
|
9 * without limitation the rights to use, copy, modify, merge, publish, |
|
10 * distribute, sublicense, and/or sell copies of the Software, and to |
|
11 * permit persons to whom the Software is furnished to do so, subject to |
|
12 * the following conditions: |
|
13 * |
|
14 * The above copyright notice and this permission notice shall be included |
|
15 * in all copies or substantial portions of the Software. |
|
16 * |
|
17 * THE SOFTWARE IS PROVIDED "AS IS", WITHOUT WARRANTY OF ANY KIND, |
|
18 * EXPRESS OR IMPLIED, INCLUDING BUT NOT LIMITED TO THE WARRANTIES OF |
|
19 * MERCHANTABILITY, FITNESS FOR A PARTICULAR PURPOSE AND NONINFRINGEMENT. |
|
20 * IN NO EVENT SHALL THE AUTHORS OR COPYRIGHT HOLDERS BE LIABLE FOR ANY |
|
21 * CLAIM, DAMAGES OR OTHER LIABILITY, WHETHER IN AN ACTION OF CONTRACT, |
|
22 * TORT OR OTHERWISE, ARISING FROM, OUT OF OR IN CONNECTION WITH THE |
|
23 * SOFTWARE OR THE USE OR OTHER DEALINGS IN THE SOFTWARE. |
|
24 * |
|
25 *********************************************************************/ |
|
26 |
|
27 /* Multi-state Input Objects */ |
|
28 |
|
29 #include <stdbool.h> |
|
30 #include <stdint.h> |
|
31 #include <stdio.h> |
|
32 |
|
33 #include "config_bacnet_for_beremiz_%(locstr)s.h" /* the custom configuration for beremiz pluginh */ |
|
34 #include "bacdef.h" |
|
35 #include "bacdcode.h" |
|
36 #include "bacenum.h" |
|
37 #include "bacapp.h" |
|
38 #include "rp.h" |
|
39 #include "wp.h" |
|
40 #include "msi_%(locstr)s.h" |
|
41 #include "handlers.h" |
|
42 |
|
43 |
|
44 /* initial value for present_value property of each object */ |
|
45 #define MSI_VALUE_INIT (1) |
|
46 |
|
47 /* The IEC 61131-3 located variables mapped onto the Multi-state Input objects of BACnet protocol */ |
|
48 %(MSI_lvars)s |
|
49 |
|
50 |
|
51 /* The array where we keep all the state related to the Multi-state Input Objects */ |
|
52 #define MAX_MULTISTATE_INPUTS %(MSI_count)s |
|
53 static MULTISTATE_INPUT_DESCR MSI_Descr[MAX_MULTISTATE_INPUTS] = { |
|
54 %(MSI_param)s |
|
55 }; |
|
56 |
|
57 |
|
58 |
|
59 /* These three arrays are used by the ReadPropertyMultiple handler, |
|
60 * as well as to initialize the XXX_Property_List used by the |
|
61 * Property List (PROP_PROPERTY_LIST) property. |
|
62 */ |
|
63 static const int Multistate_Input_Properties_Required[] = { |
|
64 /* (1) Currently Supported */ |
|
65 /* (2) Required by standard ASHRAE 135-2016 */ |
|
66 /*(1)(2) */ |
|
67 PROP_OBJECT_IDENTIFIER, /* R R ( 75) */ |
|
68 PROP_OBJECT_NAME, /* R R ( 77) */ |
|
69 PROP_OBJECT_TYPE, /* R R ( 79) */ |
|
70 PROP_PRESENT_VALUE, /* W R ( 85) */ |
|
71 PROP_STATUS_FLAGS, /* R R (111) */ |
|
72 PROP_EVENT_STATE, /* R R ( 36) */ |
|
73 PROP_OUT_OF_SERVICE, /* W R ( 81) */ |
|
74 PROP_NUMBER_OF_STATES, /* R R ( 74) */ |
|
75 // PROP_PROPERTY_LIST, /* R R (371) */ |
|
76 -1 |
|
77 }; |
|
78 |
|
79 static const int Multistate_Input_Properties_Optional[] = { |
|
80 /* (1) Currently Supported */ |
|
81 /* (2) Required by standard ASHRAE 135-2016 */ |
|
82 /*(1)(2) */ |
|
83 PROP_DESCRIPTION, /* R O ( 28) */ |
|
84 PROP_STATE_TEXT, /* R O (110) */ |
|
85 -1 |
|
86 }; |
|
87 |
|
88 static const int Multistate_Input_Properties_Proprietary[] = { |
|
89 -1 |
|
90 }; |
|
91 |
|
92 |
|
93 /* This array stores the PROPERTY_LIST which may be read by clients. |
|
94 * End of list is marked by following the last element with the value '-1' |
|
95 * |
|
96 * It is initialized by Multistate_Input_Init() based off the values |
|
97 * stored in Multistate_Input_Properties_Required |
|
98 * Multistate_Input_Properties_Optional |
|
99 * Multistate_Input_Properties_Proprietary |
|
100 */ |
|
101 /* TODO: Allocate memory for this array with malloc() at startup */ |
|
102 static int Multistate_Input_Properties_List[64]; |
|
103 |
|
104 |
|
105 |
|
106 |
|
107 |
|
108 /********************************************************/ |
|
109 /** Callback functions. **/ |
|
110 /** Functions required by BACnet devie implementation. **/ |
|
111 /********************************************************/ |
|
112 |
|
113 |
|
114 /* This is a callback function. Callback set in My_Object_Table[] array declared in device.c, */ |
|
115 void Multistate_Input_Property_Lists( |
|
116 const int **pRequired, |
|
117 const int **pOptional, |
|
118 const int **pProprietary) |
|
119 { |
|
120 if (pRequired) |
|
121 *pRequired = Multistate_Input_Properties_Required; |
|
122 if (pOptional) |
|
123 *pOptional = Multistate_Input_Properties_Optional; |
|
124 if (pProprietary) |
|
125 *pProprietary = Multistate_Input_Properties_Proprietary; |
|
126 |
|
127 return; |
|
128 } |
|
129 |
|
130 |
|
131 |
|
132 /* This is a callback function. Callback set in My_Object_Table[] array declared in device.c, */ |
|
133 void Multistate_Input_Init( |
|
134 void) |
|
135 { |
|
136 unsigned int i, j; |
|
137 |
|
138 /* initialize the Multistate_Input_Properties_List array */ |
|
139 int len = 0; |
|
140 len += BACnet_Init_Properties_List(Multistate_Input_Properties_List + len, |
|
141 Multistate_Input_Properties_Required); |
|
142 len += BACnet_Init_Properties_List(Multistate_Input_Properties_List + len, |
|
143 Multistate_Input_Properties_Optional); |
|
144 len += BACnet_Init_Properties_List(Multistate_Input_Properties_List + len, |
|
145 Multistate_Input_Properties_Proprietary); |
|
146 |
|
147 /* initialize all the analog output priority arrays to NULL */ |
|
148 for (i = 0; i < MAX_MULTISTATE_INPUTS; i++) { |
|
149 MSI_Descr[i].Present_Value = MSI_VALUE_INIT; |
|
150 for (j = 0; j < MSI_Descr[i].Number_Of_States; j++) { |
|
151 sprintf(MSI_Descr[i].State_Text[j], "State %%d", j+1); |
|
152 } |
|
153 } |
|
154 return; |
|
155 } |
|
156 |
|
157 |
|
158 |
|
159 /* validate that the given instance exists */ |
|
160 /* This is a callback function. Callback set in My_Object_Table[] array declared in device.c, */ |
|
161 bool Multistate_Input_Valid_Instance( |
|
162 uint32_t object_instance) |
|
163 { |
|
164 // fprintf(stderr, "BACnet plugin: Multistate_Input_Valid_Instance(obj_ID=%%u) called!\n", object _instance); |
|
165 return (Multistate_Input_Instance_To_Index(object_instance) < MAX_MULTISTATE_INPUTS); |
|
166 } |
|
167 |
|
168 |
|
169 /* the number of Multistate Value Objects */ |
|
170 /* This is a callback function. Callback set in My_Object_Table[] array declared in device.c, */ |
|
171 unsigned Multistate_Input_Count(void) {return MAX_MULTISTATE_INPUTS;} |
|
172 |
|
173 |
|
174 /* returns the instance (i.e. Object Identifier) that correlates to the correct index */ |
|
175 /* This is a callback function. Callback set in My_Object_Table[] array declared in device.c, */ |
|
176 uint32_t Multistate_Input_Index_To_Instance(unsigned index) {return MSI_Descr[index].Object_Identifier;} |
|
177 |
|
178 |
|
179 |
|
180 |
|
181 |
|
182 |
|
183 /* returns the index that correlates to the correct instance number (Object Identifier) */ |
|
184 unsigned Multistate_Input_Instance_To_Index( |
|
185 uint32_t object_instance) |
|
186 { |
|
187 unsigned index = 0; |
|
188 |
|
189 for (index = 0; index < MAX_MULTISTATE_INPUTS; index++) |
|
190 if (object_instance == MSI_Descr[index].Object_Identifier) |
|
191 return index; |
|
192 |
|
193 /* error, this object ID is not in our list! */ |
|
194 return MAX_MULTISTATE_INPUTS; |
|
195 } |
|
196 |
|
197 |
|
198 |
|
199 |
|
200 |
|
201 uint32_t Multistate_Input_Present_Value( |
|
202 uint32_t object_instance) |
|
203 { |
|
204 uint32_t value = MSI_VALUE_INIT; |
|
205 unsigned index = 0; /* offset from instance lookup */ |
|
206 |
|
207 index = Multistate_Input_Instance_To_Index(object_instance); |
|
208 if (index < MAX_MULTISTATE_INPUTS) |
|
209 value = MSI_Descr[index].Present_Value; |
|
210 |
|
211 return value; |
|
212 } |
|
213 |
|
214 |
|
215 |
|
216 bool Multistate_Input_Present_Value_Set( |
|
217 uint32_t object_instance, |
|
218 uint32_t value) |
|
219 { |
|
220 unsigned index = 0; /* offset from instance lookup */ |
|
221 |
|
222 index = Multistate_Input_Instance_To_Index(object_instance); |
|
223 if (index >= MAX_MULTISTATE_INPUTS) |
|
224 return false; |
|
225 |
|
226 if ((value == 0) || (value > MSI_Descr[index].Number_Of_States)) |
|
227 return false; |
|
228 |
|
229 MSI_Descr[index].Present_Value = (uint8_t) value; |
|
230 return true; |
|
231 } |
|
232 |
|
233 |
|
234 |
|
235 |
|
236 bool Multistate_Input_Out_Of_Service( |
|
237 uint32_t object_instance) |
|
238 { |
|
239 bool value = false; |
|
240 unsigned index = 0; |
|
241 |
|
242 index = Multistate_Input_Instance_To_Index(object_instance); |
|
243 if (index < MAX_MULTISTATE_INPUTS) { |
|
244 value = MSI_Descr[index].Out_Of_Service; |
|
245 } |
|
246 |
|
247 return value; |
|
248 } |
|
249 |
|
250 |
|
251 |
|
252 void Multistate_Input_Out_Of_Service_Set( |
|
253 uint32_t object_instance, |
|
254 bool value) |
|
255 { |
|
256 unsigned index = 0; |
|
257 |
|
258 index = Multistate_Input_Instance_To_Index(object_instance); |
|
259 if (index < MAX_MULTISTATE_INPUTS) { |
|
260 MSI_Descr[index].Out_Of_Service = value; |
|
261 } |
|
262 |
|
263 return; |
|
264 } |
|
265 |
|
266 |
|
267 |
|
268 static char *Multistate_Input_Description( |
|
269 uint32_t object_instance) |
|
270 { |
|
271 unsigned index = 0; /* offset from instance lookup */ |
|
272 char *pName = NULL; /* return value */ |
|
273 |
|
274 index = Multistate_Input_Instance_To_Index(object_instance); |
|
275 if (index < MAX_MULTISTATE_INPUTS) { |
|
276 pName = MSI_Descr[index].Description; |
|
277 } |
|
278 |
|
279 return pName; |
|
280 } |
|
281 |
|
282 |
|
283 |
|
284 /* This is a callback function. Callback set in My_Object_Table[] array declared in device.c, */ |
|
285 bool Multistate_Input_Object_Name( |
|
286 uint32_t object_instance, |
|
287 BACNET_CHARACTER_STRING * object_name) |
|
288 { |
|
289 unsigned index = 0; /* offset from instance lookup */ |
|
290 bool status = false; |
|
291 |
|
292 index = Multistate_Input_Instance_To_Index(object_instance); |
|
293 if (index < MAX_MULTISTATE_INPUTS) { |
|
294 status = characterstring_init_ansi(object_name, MSI_Descr[index].Object_Name); |
|
295 } |
|
296 |
|
297 return status; |
|
298 } |
|
299 |
|
300 |
|
301 |
|
302 /* return apdu len, or BACNET_STATUS_ERROR on error */ |
|
303 /* This is a callback function. Callback set in My_Object_Table[] array declared in device.c, */ |
|
304 int Multistate_Input_Read_Property( |
|
305 BACNET_READ_PROPERTY_DATA * rpdata) |
|
306 { |
|
307 int len = 0; |
|
308 int apdu_len = 0; /* return value */ |
|
309 BACNET_BIT_STRING bit_string; |
|
310 BACNET_CHARACTER_STRING char_string; |
|
311 uint32_t present_value = 0; |
|
312 unsigned object_index = 0; |
|
313 unsigned i = 0; |
|
314 bool state = false; |
|
315 uint8_t *apdu = NULL; |
|
316 |
|
317 if ((rpdata == NULL) || (rpdata->application_data == NULL) || |
|
318 (rpdata->application_data_len == 0)) { |
|
319 return 0; |
|
320 } |
|
321 |
|
322 object_index = Multistate_Input_Instance_To_Index(rpdata->object_instance); |
|
323 if (object_index >= MAX_MULTISTATE_INPUTS) { |
|
324 rpdata->error_class = ERROR_CLASS_OBJECT; |
|
325 rpdata->error_code = ERROR_CODE_UNKNOWN_OBJECT; |
|
326 return BACNET_STATUS_ERROR; |
|
327 } |
|
328 |
|
329 apdu = rpdata->application_data; |
|
330 switch (rpdata->object_property) { |
|
331 case PROP_OBJECT_IDENTIFIER: |
|
332 apdu_len = |
|
333 encode_application_object_id(&apdu[0], |
|
334 OBJECT_MULTI_STATE_INPUT, rpdata->object_instance); |
|
335 break; |
|
336 case PROP_OBJECT_NAME: |
|
337 Multistate_Input_Object_Name(rpdata->object_instance, |
|
338 &char_string); |
|
339 apdu_len = |
|
340 encode_application_character_string(&apdu[0], &char_string); |
|
341 break; |
|
342 case PROP_DESCRIPTION: |
|
343 characterstring_init_ansi(&char_string, |
|
344 Multistate_Input_Description(rpdata->object_instance)); |
|
345 apdu_len = |
|
346 encode_application_character_string(&apdu[0], &char_string); |
|
347 break; |
|
348 case PROP_OBJECT_TYPE: |
|
349 apdu_len = |
|
350 encode_application_enumerated(&apdu[0], |
|
351 OBJECT_MULTI_STATE_INPUT); |
|
352 break; |
|
353 case PROP_PRESENT_VALUE: |
|
354 present_value = |
|
355 Multistate_Input_Present_Value(rpdata->object_instance); |
|
356 apdu_len = encode_application_unsigned(&apdu[0], present_value); |
|
357 break; |
|
358 case PROP_STATUS_FLAGS: |
|
359 /* note: see the details in the standard on how to use these */ |
|
360 bitstring_init(&bit_string); |
|
361 bitstring_set_bit(&bit_string, STATUS_FLAG_IN_ALARM, false); |
|
362 bitstring_set_bit(&bit_string, STATUS_FLAG_FAULT, false); |
|
363 bitstring_set_bit(&bit_string, STATUS_FLAG_OVERRIDDEN, false); |
|
364 if (Multistate_Input_Out_Of_Service(rpdata->object_instance)) { |
|
365 bitstring_set_bit(&bit_string, STATUS_FLAG_OUT_OF_SERVICE, |
|
366 true); |
|
367 } else { |
|
368 bitstring_set_bit(&bit_string, STATUS_FLAG_OUT_OF_SERVICE, |
|
369 false); |
|
370 } |
|
371 apdu_len = encode_application_bitstring(&apdu[0], &bit_string); |
|
372 break; |
|
373 case PROP_EVENT_STATE: |
|
374 /* note: see the details in the standard on how to use this */ |
|
375 apdu_len = |
|
376 encode_application_enumerated(&apdu[0], EVENT_STATE_NORMAL); |
|
377 break; |
|
378 case PROP_OUT_OF_SERVICE: |
|
379 state = MSI_Descr[object_index].Out_Of_Service; |
|
380 apdu_len = encode_application_boolean(&apdu[0], state); |
|
381 break; |
|
382 case PROP_NUMBER_OF_STATES: |
|
383 apdu_len = |
|
384 encode_application_unsigned(&apdu[apdu_len], |
|
385 MSI_Descr[object_index].Number_Of_States); |
|
386 break; |
|
387 case PROP_STATE_TEXT: |
|
388 BACnet_encode_array(MSI_Descr[object_index].State_Text, |
|
389 MSI_Descr[object_index].Number_Of_States, |
|
390 retfalse, BACnet_encode_character_string); |
|
391 break; |
|
392 // case PROP_PROPERTY_LIST: |
|
393 // BACnet_encode_array(Multistate_Input_Properties_List, |
|
394 // property_list_count(Multistate_Input_Properties_List), |
|
395 // retfalse, encode_application_enumerated); |
|
396 // break; |
|
397 default: |
|
398 rpdata->error_class = ERROR_CLASS_PROPERTY; |
|
399 rpdata->error_code = ERROR_CODE_UNKNOWN_PROPERTY; |
|
400 apdu_len = BACNET_STATUS_ERROR; |
|
401 break; |
|
402 } |
|
403 /* only array properties can have array options */ |
|
404 if ((apdu_len >= 0) && (rpdata->object_property != PROP_STATE_TEXT) && |
|
405 // (rpdata->object_property != PROP_PROPERTY_LIST) && |
|
406 (rpdata->array_index != BACNET_ARRAY_ALL)) { |
|
407 rpdata->error_class = ERROR_CLASS_PROPERTY; |
|
408 rpdata->error_code = ERROR_CODE_PROPERTY_IS_NOT_AN_ARRAY; |
|
409 apdu_len = BACNET_STATUS_ERROR; |
|
410 } |
|
411 |
|
412 return apdu_len; |
|
413 } |
|
414 |
|
415 /* returns true if successful */ |
|
416 /* This is a callback function. Callback set in My_Object_Table[] array declared in device.c, */ |
|
417 bool Multistate_Input_Write_Property( |
|
418 BACNET_WRITE_PROPERTY_DATA * wp_data) |
|
419 { |
|
420 bool status = false; /* return value */ |
|
421 int len = 0; |
|
422 unsigned object_index = 0; |
|
423 BACNET_APPLICATION_DATA_VALUE value; |
|
424 |
|
425 /* decode the some of the request */ |
|
426 len = |
|
427 bacapp_decode_application_data(wp_data->application_data, |
|
428 wp_data->application_data_len, &value); |
|
429 /* FIXME: len < application_data_len: more data? */ |
|
430 if (len < 0) { |
|
431 /* error while decoding - a value larger than we can handle */ |
|
432 wp_data->error_class = ERROR_CLASS_PROPERTY; |
|
433 wp_data->error_code = ERROR_CODE_VALUE_OUT_OF_RANGE; |
|
434 return false; |
|
435 } |
|
436 if ((wp_data->object_property != PROP_STATE_TEXT) && |
|
437 (wp_data->array_index != BACNET_ARRAY_ALL)) { |
|
438 /* only array properties can have array options */ |
|
439 wp_data->error_class = ERROR_CLASS_PROPERTY; |
|
440 wp_data->error_code = ERROR_CODE_PROPERTY_IS_NOT_AN_ARRAY; |
|
441 return false; |
|
442 } |
|
443 /* No need to check whether object_index is within bounds. |
|
444 * Has already been checked before Multistate_Input_Write_Property() is called |
|
445 */ |
|
446 object_index = Multistate_Input_Instance_To_Index(wp_data->object_instance); |
|
447 |
|
448 switch (wp_data->object_property) { |
|
449 case PROP_PRESENT_VALUE: |
|
450 status = |
|
451 WPValidateArgType(&value, BACNET_APPLICATION_TAG_UNSIGNED_INT, |
|
452 &wp_data->error_class, &wp_data->error_code); |
|
453 if (!status) { |
|
454 wp_data->error_class = ERROR_CLASS_PROPERTY; |
|
455 wp_data->error_code = ERROR_CODE_INVALID_DATA_TYPE; |
|
456 status = false; // not really necessary here. |
|
457 } else { |
|
458 if (!MSI_Descr[object_index].Out_Of_Service) { |
|
459 /* input objects can only be written to when Out_Of_Service is true! */ |
|
460 wp_data->error_class = ERROR_CLASS_PROPERTY; |
|
461 wp_data->error_code = ERROR_CODE_WRITE_ACCESS_DENIED; |
|
462 status = false; |
|
463 } else { |
|
464 status = |
|
465 Multistate_Input_Present_Value_Set |
|
466 (wp_data->object_instance, value.type.Unsigned_Int); |
|
467 if (!status) { |
|
468 wp_data->error_class = ERROR_CLASS_PROPERTY; |
|
469 wp_data->error_code = ERROR_CODE_VALUE_OUT_OF_RANGE; |
|
470 status = false; // not really necessary here. |
|
471 } |
|
472 } |
|
473 } |
|
474 break; |
|
475 case PROP_OUT_OF_SERVICE: |
|
476 { |
|
477 bool Previous_Out_Of_Service = MSI_Descr[object_index].Out_Of_Service; |
|
478 status = |
|
479 WPValidateArgType(&value, BACNET_APPLICATION_TAG_BOOLEAN, |
|
480 &wp_data->error_class, &wp_data->error_code); |
|
481 if (status) { |
|
482 MSI_Descr[object_index].Out_Of_Service = value.type.Boolean; |
|
483 if (Previous_Out_Of_Service && !MSI_Descr[object_index].Out_Of_Service) |
|
484 /* We have just changed from Out_of_Service -> In Service */ |
|
485 /* We need to update the Present_Value to the value |
|
486 * currently in the PLC... |
|
487 */ |
|
488 MSI_Descr[object_index].Present_Value = |
|
489 *(MSI_Descr[object_index].Located_Var_ptr); |
|
490 } |
|
491 break; |
|
492 } |
|
493 case PROP_OBJECT_IDENTIFIER: |
|
494 case PROP_OBJECT_NAME: |
|
495 case PROP_OBJECT_TYPE: |
|
496 case PROP_STATUS_FLAGS: |
|
497 case PROP_EVENT_STATE: |
|
498 case PROP_NUMBER_OF_STATES: |
|
499 case PROP_DESCRIPTION: |
|
500 case PROP_STATE_TEXT: |
|
501 // case PROP_PROPERTY_LIST: |
|
502 wp_data->error_class = ERROR_CLASS_PROPERTY; |
|
503 wp_data->error_code = ERROR_CODE_WRITE_ACCESS_DENIED; |
|
504 break; |
|
505 default: |
|
506 wp_data->error_class = ERROR_CLASS_PROPERTY; |
|
507 wp_data->error_code = ERROR_CODE_UNKNOWN_PROPERTY; |
|
508 break; |
|
509 } |
|
510 |
|
511 return status; |
|
512 } |
|
513 |
|
514 |
|
515 |
|
516 |
|
517 |
|
518 /********************************************/ |
|
519 /** Functions required for Beremiz plugin **/ |
|
520 /********************************************/ |
|
521 |
|
522 |
|
523 |
|
524 void Multistate_Input_Copy_Present_Value_to_Located_Var(void) { |
|
525 unsigned i; |
|
526 for (i = 0; i < MAX_MULTISTATE_INPUTS; i++) { |
|
527 // decouple PLC's Located Variable from Bacnet Object's Present Value if Out_Of_Service is true |
|
528 if (MSI_Descr[i].Out_Of_Service) |
|
529 continue; |
|
530 |
|
531 // copy the value |
|
532 *(MSI_Descr[i].Located_Var_ptr) = Multistate_Input_Present_Value(MSI_Descr[i].Object_Identifier); |
|
533 } |
|
534 } |
|
535 |
|
536 |
|
537 |
|
538 void Multistate_Input_Copy_Located_Var_to_Present_Value(void) { |
|
539 unsigned i; |
|
540 for (i = 0; i < MAX_MULTISTATE_INPUTS; i++) { |
|
541 // decouple PLC's Located Variable from Bacnet Object's Present Value if Out_Of_Service is true |
|
542 if (MSI_Descr[i].Out_Of_Service) |
|
543 continue; |
|
544 |
|
545 // Make sure local device does not set Present_Value to 0, nor higher than Number_Of_States |
|
546 if ((*(MSI_Descr[i].Located_Var_ptr) > MSI_Descr[i].Number_Of_States) || |
|
547 (*(MSI_Descr[i].Located_Var_ptr) == 0)) |
|
548 continue; |
|
549 |
|
550 // Everything seems to be OK. Copy the value |
|
551 MSI_Descr[i].Present_Value = *(MSI_Descr[i].Located_Var_ptr); |
|
552 } |
|
553 } |
|
554 |
|
555 |
|
556 |