CRC-Counter nach ESC-Datasheet implementiert.
--- a/master/slave.c Mon Mar 27 10:47:12 2006 +0000
+++ b/master/slave.c Mon Mar 27 12:04:55 2006 +0000
@@ -871,14 +871,31 @@
}
// No CRC faults.
- if (!EC_READ_U16(command.data) && !EC_READ_U16(command.data + 2)) return 0;
-
- EC_WARN("CRC faults on slave %i. A: %i, B: %i\n", slave->ring_position,
- EC_READ_U16(command.data), EC_READ_U16(command.data + 2));
+ if (!EC_READ_U32(command.data)) return 0;
+
+ if (EC_READ_U8(command.data))
+ EC_WARN("%3i RX-error%s on slave %i, channel A.\n",
+ EC_READ_U8(command.data),
+ EC_READ_U8(command.data) == 1 ? "" : "s",
+ slave->ring_position);
+ if (EC_READ_U8(command.data + 1))
+ EC_WARN("%3i invalid frame%s on slave %i, channel A.\n",
+ EC_READ_U8(command.data + 1),
+ EC_READ_U8(command.data + 1) == 1 ? "" : "s",
+ slave->ring_position);
+ if (EC_READ_U8(command.data + 2))
+ EC_WARN("%3i RX-error%s on slave %i, channel B.\n",
+ EC_READ_U8(command.data + 2),
+ EC_READ_U8(command.data + 2) == 1 ? "" : "s",
+ slave->ring_position);
+ if (EC_READ_U8(command.data + 3))
+ EC_WARN("%3i invalid frame%s on slave %i, channel B.\n",
+ EC_READ_U8(command.data + 3),
+ EC_READ_U8(command.data + 3) == 1 ? "" : "s",
+ slave->ring_position);
// Reset CRC counters
- EC_WRITE_U16(data, 0x0000);
- EC_WRITE_U16(data + 2, 0x0000);
+ EC_WRITE_U32(data, 0x00000000);
ec_command_init_npwr(&command, slave->station_address, 0x0300, 4, data);
if (unlikely(ec_master_simple_io(slave->master, &command))) {
EC_WARN("Resetting CRC fault counters failed on slave %i!\n",
--- a/todo.txt Mon Mar 27 10:47:12 2006 +0000
+++ b/todo.txt Mon Mar 27 12:04:55 2006 +0000
@@ -5,12 +5,12 @@
- Anzahl Frames, die die Karte Puffern kann
- Mehrere Frames versenden
+- Typeninformation aus Master entfernen / XML-Dateien aus User-Space lesen
- Kommandos mit dynamischem Speicher
- Konfiguration Inkrementalgeberklemme
- SSI-Klemme
- SysFS-Interface implementieren
- SDO Dictionary der Slaves auslesen und im SysFS darstellen
-- Typeninformation aus Master entfernen / XML-Dateien aus User-Space lesen
- DLL-Link-States auslesen und Topologie berechnen
- Ethernet over EtherCAT (EoE)
- eepro100-Kartentreiber