* Copyright (C) 2006 Steve Karg <skarg@users.sourceforge.net>
* Copyright (C) 2017 Mario de Sousa <msousa@fe.up.pt>
*
* Permission is hereby granted, free of charge, to any person obtaining
* a copy of this software and associated documentation files (the
* "Software"), to deal in the Software without restriction, including
* without limitation the rights to use, copy, modify, merge, publish,
* distribute, sublicense, and/or sell copies of the Software, and to
* permit persons to whom the Software is furnished to do so, subject to
* the following conditions:
*
* The above copyright notice and this permission notice shall be included
* in all copies or substantial portions of the Software.
*
* THE SOFTWARE IS PROVIDED "AS IS", WITHOUT WARRANTY OF ANY KIND,
* EXPRESS OR IMPLIED, INCLUDING BUT NOT LIMITED TO THE WARRANTIES OF
* MERCHANTABILITY, FITNESS FOR A PARTICULAR PURPOSE AND NONINFRINGEMENT.
* IN NO EVENT SHALL THE AUTHORS OR COPYRIGHT HOLDERS BE LIABLE FOR ANY
* CLAIM, DAMAGES OR OTHER LIABILITY, WHETHER IN AN ACTION OF CONTRACT,
* TORT OR OTHERWISE, ARISING FROM, OUT OF OR IN CONNECTION WITH THE
* SOFTWARE OR THE USE OR OTHER DEALINGS IN THE SOFTWARE.
*
*********************************************************************/
#include <stddef.h>
#include <stdint.h>
#include <stdio.h>
#include <stdlib.h>
#include <signal.h>
#include <time.h>
#include <inttypes.h> // uint32_t, ..., PRIu32, ...
#include "config_bacnet_for_beremiz_%(locstr)s.h" /* the custom configuration for beremiz pluginh */
#include "server_%(locstr)s.h"
#include "address.h"
#include "bacdef.h"
#include "handlers.h"
#include "client.h"
#include "dlenv.h"
#include "bacdcode.h"
#include "npdu.h"
#include "apdu.h"
#include "iam.h"
#include "tsm.h"
#include "datalink.h"
#include "dcc.h"
#include "getevent.h"
#include "net.h"
#include "txbuf.h"
#include "version.h"
#include "timesync.h"
/* A utility function used by most (all?) implementations of BACnet Objects */
/* Adds to Prop_List all entries in Prop_List_XX that are not
* PROP_OBJECT_IDENTIFIER, PROP_OBJECT_NAME, PROP_OBJECT_TYPE, PROP_PROPERTY_LIST
* and returns the number of elements that were added
*/
int BACnet_Init_Properties_List(
int *Prop_List,
const int *Prop_List_XX) {
unsigned int i = 0;
unsigned int j = 0;
for (j = 0; Prop_List_XX[j] >= 0; j++)
// Add any propety, except for the following 4 which should not be included
// in the Property_List property array.
// (see ASHRAE 135-2016, for example section 12.4.34)
if ((Prop_List_XX[j] != PROP_OBJECT_IDENTIFIER) &&
(Prop_List_XX[j] != PROP_OBJECT_NAME) &&
(Prop_List_XX[j] != PROP_OBJECT_TYPE) &&
(Prop_List_XX[j] != PROP_PROPERTY_LIST)) {
Prop_List[i] = Prop_List_XX[j];
i++;
}
Prop_List[i] = -1; // marks the end of the list!
return i;
}
int BACnet_encode_character_string(uint8_t *apdu, const char *str) {
BACNET_CHARACTER_STRING char_string;
characterstring_init_ansi(&char_string, str);
/* FIXME: this might go beyond MAX_APDU length! */
return encode_application_character_string(apdu, &char_string);
}
/* macro that always returns false.
* To be used as the 'test_null' parameter to the BACnet_encode_array macro
* in situations where we should never encode_null() values.
*/
#define retfalse(x) (false)
#define BACnet_encode_array(array, array_len, test_null, encode_function) \
{ \
uint8_t *apdu = NULL; \
apdu = rpdata->application_data; \
\
switch (rpdata->array_index) { \
case 0: /* Array element zero is the number of elements in the array */ \
apdu_len = encode_application_unsigned(&apdu[0], array_len); \
break; \
case BACNET_ARRAY_ALL: { \
/* if no index was specified, then try to encode the entire list */ \
unsigned i = 0; \
apdu_len = 0; \
for (i = 0; i < array_len; i++) { \
/* FIXME: this might go beyond MAX_APDU length! */ \
if (!test_null(array[i])) \
apdu_len += encode_function (&apdu[apdu_len], array[i]); \
else apdu_len += encode_application_null(&apdu[apdu_len]); \
/* return error if it does not fit in the APDU */ \
if (apdu_len >= MAX_APDU) { \
rpdata->error_class = ERROR_CLASS_SERVICES; \
rpdata->error_code = ERROR_CODE_NO_SPACE_FOR_OBJECT; \
apdu_len = BACNET_STATUS_ERROR; \
break; /* for(;;) */ \
} \
} \
break; \
} \
default: \
if (rpdata->array_index <= array_len) { \
if (!test_null(array[rpdata->array_index - 1])) \
apdu_len += encode_function(&apdu[0], array[rpdata->array_index - 1]); \
else apdu_len += encode_application_null(&apdu[0]); \
} else { \
rpdata->error_class = ERROR_CLASS_PROPERTY; \
rpdata->error_code = ERROR_CODE_INVALID_ARRAY_INDEX; \
apdu_len = BACNET_STATUS_ERROR; \
} \
break; \
} /* switch() */ \
}
/* include the device object */
#include "device_%(locstr)s.c"
#include "ai_%(locstr)s.c"
#include "ao_%(locstr)s.c"
#include "av_%(locstr)s.c"
#include "bi_%(locstr)s.c"
#include "bo_%(locstr)s.c"
#include "bv_%(locstr)s.c"
#include "msi_%(locstr)s.c"
#include "mso_%(locstr)s.c"
#include "msv_%(locstr)s.c"
/** Buffer used for receiving */
static uint8_t Rx_Buf[MAX_MPDU] = { 0 };
/*******************************************************/
/* BACnet Service Handlers taylored to Beremiz plugin */
/*******************************************************/
static void BACNET_show_date_time(
BACNET_DATE * bdate,
BACNET_TIME * btime)
{
/* show the date received */
fprintf(stderr, "%%u", (unsigned) bdate->year);
fprintf(stderr, "/%%u", (unsigned) bdate->month);
fprintf(stderr, "/%%u", (unsigned) bdate->day);
/* show the time received */
fprintf(stderr, " %%02u", (unsigned) btime->hour);
fprintf(stderr, ":%%02u", (unsigned) btime->min);
fprintf(stderr, ":%%02u", (unsigned) btime->sec);
fprintf(stderr, ".%%02u", (unsigned) btime->hundredths);
fprintf(stderr, "\r\n");
}
static time_t __timegm(struct tm *new_time) {
time_t sec = mktime(new_time); /* assume new_time is in local time */
/* sec will be an aproximation of the correct value.
* We must now fix this with the current difference
* between UTC and localtime.
*
* WARNING: The following algorithm to determine the current
* difference between local time and UTC will not
* work if each value (lcl and utc) falls on a different
* side of a change to/from DST.
* For example, assume a change to DST is made at 12h00
* of day X. The following algorithm does not work if:
* - lcl falls before 12h00 of day X
* - utc falls after 12h00 of day X
*/
struct tm lcl = *localtime(&sec); // lcl will be == new_time
struct tm utc = *gmtime (&sec);
if (lcl.tm_isdst == 1) utc.tm_isdst = 1;
time_t sec_lcl = mktime(&lcl);
time_t sec_utc = mktime(&utc);
/* difference in seconds between localtime and utc */
time_t sec_dif = sec_lcl - sec_utc;
return sec + sec_dif;
}
static void BACNET_set_date_time(
BACNET_DATE * bdate,
BACNET_TIME * btime,
int utc /* set to > 0 if date & time in UTC */)
{
struct tm brokendown_time;
time_t seconds = 0;
struct timespec ts;
brokendown_time.tm_sec = btime->sec; /* seconds 0..60 */
brokendown_time.tm_min = btime->min; /* minutes 0..59 */
brokendown_time.tm_hour = btime->hour; /* hours 0..23 */
brokendown_time.tm_mday = bdate->day; /* day of the month 1..31 */
brokendown_time.tm_mon = bdate->month-1; /* month 0..11 */
brokendown_time.tm_year = bdate->year-1900; /* years since 1900 */
// brokendown_time.tm_wday = ; /* day of the week */
// brokendown_time.tm_yday = ; /* day in the year */
brokendown_time.tm_isdst = -1; /* daylight saving time (-1 => unknown) */
// Tranform time into format -> 'seconds since epoch'
/* WARNING: timegm() is a non standard GNU extension.
* If you do not have it on your build system then consider
* finding the source code for timegm() (it is LGPL) from GNU
* C library and copying it here
* (e.g. https://code.woboq.org/userspace/glibc/time/timegm.c.html)
* Another alternative is to use the fundion __timegm() above,
* which will mostly work but may have errors when the time being
* converted is close to the time in the year when changing
* to/from DST (daylight saving time)
*/
if (utc > 0) seconds = timegm(&brokendown_time);
else seconds = mktime(&brokendown_time);
ts.tv_sec = seconds;
ts.tv_nsec = btime->hundredths*10*1000*1000;
// fprintf(stderr, "clock_settime() s=%%ul, ns=%%u\n", ts.tv_sec, ts.tv_nsec);
clock_settime(CLOCK_REALTIME, &ts);
// clock_gettime(CLOCK_REALTIME, &ts);
// fprintf(stderr, "clock_gettime() s=%%ul, ns=%%u\n", ts.tv_sec, ts.tv_nsec);
}
void BACnet_handler_timesync(
uint8_t * service_request,
uint16_t service_len,
BACNET_ADDRESS * src)
{
int len = 0;
BACNET_DATE bdate;
BACNET_TIME btime;
(void) src;
(void) service_len;
len =
timesync_decode_service_request(service_request, service_len, &bdate, &btime);
if (len > 0) {
fprintf(stderr, "BACnet plugin: Received TimeSyncronization Request -> ");
BACNET_show_date_time(&bdate, &btime);
/* set the time */
BACNET_set_date_time(&bdate, &btime, 0 /* time in local time */);
}
return;
}
void BACnet_handler_timesync_utc(
uint8_t * service_request,
uint16_t service_len,
BACNET_ADDRESS * src)
{
int len = 0;
BACNET_DATE bdate;
BACNET_TIME btime;
(void) src;
(void) service_len;
len =
timesync_decode_service_request(service_request, service_len, &bdate, &btime);
if (len > 0) {
fprintf(stderr, "BACnet plugin: Received TimeSyncronizationUTC Request -> ");
BACNET_show_date_time(&bdate, &btime);
/* set the time */
BACNET_set_date_time(&bdate, &btime, 1 /* time in UTC */);
}
return;
}
/**********************************************/
/** Initialize the handlers we will utilize. **/
/**********************************************/
/*
* TLDR: The functions that will create the __Resp.__ messages.
*
* The service handlers are the functions that will respond to BACnet requests this device receives.
* In essence, the service handlers will create and send the Resp. (Response) messages
* of the Req. -> Ind. -> Resp. -> Conf. service sequence defined in OSI
* (Request, Indication, Response, Confirmation)
*
*/
static int Init_Service_Handlers(
void)
{
/* set the handler for all the services we don't implement */
/* It is required to send the proper reject message... */
apdu_set_unrecognized_service_handler_handler(handler_unrecognized_service);
/* Set the handlers for any unconfirmed services that we support. */
apdu_set_unconfirmed_handler(SERVICE_UNCONFIRMED_WHO_IS, // DM-DDB-B - Dynamic Device Binding B (Resp.)
handler_who_is); // (see ASHRAE 135-2016, section K5.1 and K5.2)
// apdu_set_unconfirmed_handler(SERVICE_UNCONFIRMED_I_AM, // DM-DDB-A - Dynamic Device Binding A (Resp.)
// handler_i_am_bind); // Responding to I_AM requests is for clients (A)!
// // (see ASHRAE 135-2016, section K5.1 and K5.2)
apdu_set_unconfirmed_handler(SERVICE_UNCONFIRMED_WHO_HAS, // DM-DOB-B - Dynamic Object Binding B (Resp.)
handler_who_has); // (see ASHRAE 135-2016, section K5.3 and K5.4)
// apdu_set_unconfirmed_handler(SERVICE_UNCONFIRMED_I_HAVE, // DM-DOB-A - Dynamic Object Binding A (Resp.)
// handler_i_have); // Responding to I_HAVE requests is for clients (A)!
// // (see ASHRAE 135-2016, section K5.3 and K5.4)
apdu_set_unconfirmed_handler(SERVICE_UNCONFIRMED_UTC_TIME_SYNCHRONIZATION, // DM-UTC-B -UTCTimeSynchronization-B (Resp.)
BACnet_handler_timesync_utc); // (see ASHRAE 135-2016, section K5.14)
apdu_set_unconfirmed_handler(SERVICE_UNCONFIRMED_TIME_SYNCHRONIZATION, // DM-TS-B - TimeSynchronization-B (Resp.)
BACnet_handler_timesync); // (see ASHRAE 135-2016, section K5.12)
/* Set the handlers for any confirmed services that we support. */
apdu_set_confirmed_handler(SERVICE_CONFIRMED_READ_PROPERTY, // DS-RP-B - Read Property B (Resp.)
handler_read_property); // (see ASHRAE 135-2016, section K1.2)
// apdu_set_confirmed_handler(SERVICE_CONFIRMED_READ_PROP_MULTIPLE, // DS-RPM-B -Read Property Multiple-B (Resp.)
// handler_read_property_multiple); // (see ASHRAE 135-2016, section K1.4)
apdu_set_confirmed_handler(SERVICE_CONFIRMED_WRITE_PROPERTY, // DS-WP-B - Write Property B (Resp.)
handler_write_property); // (see ASHRAE 135-2016, section K1.8)
// apdu_set_confirmed_handler(SERVICE_CONFIRMED_WRITE_PROP_MULTIPLE,// DS-WPM-B -Write Property Multiple B (Resp.)
// handler_write_property_multiple); // (see ASHRAE 135-2016, section K1.10)
// apdu_set_confirmed_handler(SERVICE_CONFIRMED_READ_RANGE,
// handler_read_range);
// apdu_set_confirmed_handler(SERVICE_CONFIRMED_REINITIALIZE_DEVICE,
// handler_reinitialize_device);
// apdu_set_confirmed_handler(SERVICE_CONFIRMED_SUBSCRIBE_COV,
// handler_cov_subscribe);
// apdu_set_unconfirmed_handler(SERVICE_UNCONFIRMED_COV_NOTIFICATION,
// handler_ucov_notification);
/* handle communication so we can shutup when asked */
apdu_set_confirmed_handler(SERVICE_CONFIRMED_DEVICE_COMMUNICATION_CONTROL, // DM-DCC-B - Device Communication Control B
handler_device_communication_control); // (see ASHRAE 135-2016, section K5.6)
// /* handle the data coming back from private requests */
// apdu_set_unconfirmed_handler(SERVICE_UNCONFIRMED_PRIVATE_TRANSFER,
// handler_unconfirmed_private_transfer);
// success
return 0;
}
static int Init_Network_Interface(
const char *interface, // for linux: /dev/eth0, /dev/eth1, /dev/wlan0, ...
// for windows: 192.168.0.1 (IP addr. of interface)
// NULL => use default!
const char *port, // Port the server will listen on. (NULL => use default)
const char *apdu_timeout, // (NULL => use default)
const char *apdu_retries // (NULL => use default)
)
{
char datalink_layer[4];
strcpy(datalink_layer, "BIP"); // datalink_set() does not accpet const char *, so we copy it...
// BIP_Debug = true;
if (port != NULL) {
bip_set_port(htons((uint16_t) strtol(port, NULL, 0)));
} else {
bip_set_port(htons(0xBAC0));
}
if (apdu_timeout != NULL) {
apdu_timeout_set((uint16_t) strtol(apdu_timeout, NULL, 0));
}
if (apdu_retries != NULL) {
apdu_retries_set((uint8_t) strtol(apdu_retries, NULL, 0));
}
// datalink_init is a pointer that will actually call bip_init()
// datalink_init pointer is set by the call datalink_set("BIP")
/* NOTE: current implementation of BACnet stack uses the interface
* only to determine the server's local IP address and broacast address.
* The local IP addr is later used to discard (broadcast) messages
* it receives that were sent by itself.
* The broadcast IP addr is used for broadcast messages.
* WARNING: The socket itself is created to listen on all
* available interfaces (INADDR_ANY), so this setting may induce
* the user in error as we will accept messages arriving on other
* interfaces (if they exist)
* (see bip_init() in ports/linux/bip-init.c)
* (see bip_****() in src/bip.c)
*/
char *tmp = (char *)malloc(strlen(interface) + 1);
if (tmp == NULL) return -1;
strncpy(tmp, interface, strlen(interface) + 1);
if (!datalink_init(tmp)) {
return -1;
}
// #if (MAX_TSM_TRANSACTIONS)
// pEnv = getenv("BACNET_INVOKE_ID");
// if (pEnv) {
// tsm_invokeID_set((uint8_t) strtol(pEnv, NULL, 0));
// }
// #endif
dlenv_register_as_foreign_device();
// success
return 0;
}
// This mutex blocks execution of __init_%(locstr)s() until initialization is done
static int init_done = 0;
static pthread_mutex_t init_done_lock = PTHREAD_MUTEX_INITIALIZER;
static pthread_cond_t init_done_cond = PTHREAD_COND_INITIALIZER;
/** Main function of server demo. **/
int bn_server_run(server_node_t *server_node) {
int res = 0;
BACNET_ADDRESS src = {0}; /* address where message came from */
uint16_t pdu_len = 0;
unsigned timeout = 1000; /* milliseconds */
time_t last_seconds = 0;
time_t current_seconds = 0;
uint32_t elapsed_seconds = 0;
uint32_t elapsed_milliseconds = 0;
uint32_t address_binding_tmr = 0;
uint32_t recipient_scan_tmr = 0;
/* allow the device ID to be set */
Device_Set_Object_Instance_Number(server_node->device_id);
/* load any static address bindings in our device bindings list */
address_init();
/* load any entries in the BDT table from backup file */
bvlc_bdt_restore_local();
/* Initiliaze the bacnet server 'device' */
Device_Init(server_node->device_name);
pthread_mutex_lock(&init_done_lock);
init_done = 1;
pthread_cond_signal(&init_done_cond);
pthread_mutex_unlock(&init_done_lock);
/* Set the password (max 31 chars) for Device Communication Control request. */
/* Default in the BACnet stack is hardcoded as "filister" */
/* (char *) cast is to remove the cast. The function is incorrectly declared/defined in the BACnet stack! */
/* BACnet stack needs to change demo/handler/h_dcc.c and include/handlers.h */
handler_dcc_password_set((char *)server_node->comm_control_passwd);
/* Set callbacks and configure network interface */
res = Init_Service_Handlers();
if (res < 0) exit(1);
res = Init_Network_Interface(
server_node->network_interface, // interface (NULL => use default (eth0))
server_node->port_number, // Port number (NULL => use default (0xBAC0))
NULL, // apdu_timeout (NULL => use default)
NULL // apdu_retries (NULL => use default)
);
if (res < 0) {
fprintf(stderr, "BACnet plugin: error initializing bacnet server node %%s!\n", server_node->location);
exit(1); // kill the server thread!
}
/* BACnet stack correcly configured. Give user some feedback! */
struct in_addr my_addr, broadcast_addr;
my_addr. s_addr = bip_get_addr();
broadcast_addr.s_addr = bip_get_broadcast_addr();
printf("BACnet plugin:"
" Local IP addr: %%s"
", Broadcast IP addr: %%s"
", Port number: 0x%%04X [%%hu]"
", BACnet Device ID: %%d"
", Max APDU: %%d"
", BACnet Stack Version %%s\n",
inet_ntoa(my_addr),
inet_ntoa(broadcast_addr),
ntohs(bip_get_port()), ntohs(bip_get_port()),
Device_Object_Instance_Number(),
MAX_APDU,
Device_Firmware_Revision()
);
/* configure the timeout values */
last_seconds = time(NULL);
/* broadcast an I-Am on startup */
Send_I_Am(&Handler_Transmit_Buffer[0]);
/* loop forever */
for (;;) {
/* input */
current_seconds = time(NULL);
/* returns 0 bytes on timeout */
pdu_len = datalink_receive(&src, &Rx_Buf[0], MAX_MPDU, timeout);
/* process */
if (pdu_len) {
npdu_handler(&src, &Rx_Buf[0], pdu_len);
}
/* at least one second has passed */
elapsed_seconds = (uint32_t) (current_seconds - last_seconds);
if (elapsed_seconds) {
last_seconds = current_seconds;
dcc_timer_seconds(elapsed_seconds);
bvlc_maintenance_timer(elapsed_seconds);
dlenv_maintenance_timer(elapsed_seconds);
elapsed_milliseconds = elapsed_seconds * 1000;
tsm_timer_milliseconds(elapsed_milliseconds);
}
handler_cov_task();
/* scan cache address */
address_binding_tmr += elapsed_seconds;
if (address_binding_tmr >= 60) {
address_cache_timer(address_binding_tmr);
address_binding_tmr = 0;
}
}
/* should never occur!! */
return 0;
}
#include <pthread.h>
static void *__bn_server_thread(void *_server_node) {
server_node_t *server_node = _server_node;
// Enable thread cancelation. Enabled is default, but set it anyway to be safe.
pthread_setcancelstate(PTHREAD_CANCEL_ENABLE, NULL);
// bn_server_run() should never return!
bn_server_run(server_node);
fprintf(stderr, "BACnet plugin: bacnet server for node %%s died unexpectedly!\n", server_node->location); /* should never occur */
return NULL;
}
int __cleanup_%(locstr)s ();
int __init_%(locstr)s (int argc, char **argv){
int index;
init_done = 0;
/* init each local server */
/* NOTE: All server_nodes[].init_state are initialised to 0 in the code
* generated by the BACnet plugin
*/
/* create the BACnet server */
server_node.init_state = 1; // we have created the node
/* launch a thread to handle this server node */
{
int res = 0;
pthread_attr_t attr;
res |= pthread_attr_init(&attr);
res |= pthread_create(&(server_node.thread_id), &attr, &__bn_server_thread, (void *)&(server_node));
if (res != 0) {
fprintf(stderr, "BACnet plugin: Error starting bacnet server thread for node %%s\n", server_node.location);
goto error_exit;
}
}
pthread_mutex_lock(&init_done_lock);
while (!init_done) {
pthread_cond_wait(&init_done_cond, &init_done_lock);
}
pthread_mutex_unlock(&init_done_lock);
server_node.init_state = 2; // we have created the node and thread
return 0;
error_exit:
__cleanup_%(locstr)s ();
return -1;
}
void __publish_%(locstr)s (){
Analog_Value_Copy_Located_Var_to_Present_Value();
Analog_Input_Copy_Located_Var_to_Present_Value();
Analog_Output_Copy_Located_Var_to_Present_Value();
Binary_Value_Copy_Located_Var_to_Present_Value();
Binary_Input_Copy_Located_Var_to_Present_Value();
Binary_Output_Copy_Located_Var_to_Present_Value();
Multistate_Value_Copy_Located_Var_to_Present_Value();
Multistate_Input_Copy_Located_Var_to_Present_Value();
Multistate_Output_Copy_Located_Var_to_Present_Value();
}
void __retrieve_%(locstr)s (){
Analog_Value_Copy_Present_Value_to_Located_Var();
Analog_Input_Copy_Present_Value_to_Located_Var();
Analog_Output_Copy_Present_Value_to_Located_Var();
Binary_Value_Copy_Present_Value_to_Located_Var();
Binary_Input_Copy_Present_Value_to_Located_Var();
Binary_Output_Copy_Present_Value_to_Located_Var();
Multistate_Value_Copy_Present_Value_to_Located_Var();
Multistate_Input_Copy_Present_Value_to_Located_Var();
Multistate_Output_Copy_Present_Value_to_Located_Var();
}
int __cleanup_%(locstr)s (){
int index, close;
int res = 0;
/* kill thread and close connections of each modbus server node */
close = 0;
if (server_node.init_state >= 2) {
// thread was launched, so we try to cancel it!
close = pthread_cancel(server_node.thread_id);
close |= pthread_join (server_node.thread_id, NULL);
if (close < 0)
fprintf(stderr, "BACnet plugin: Error closing thread for bacnet server %%s\n", server_node.location);
}
res |= close;
close = 0;
if (server_node.init_state >= 1) {
// bacnet server node was created, so we try to close it!
// datalink_cleanup is a pointer that will actually call bip_cleanup()
// datalink_cleanup pointer is set by the call datalink_set("BIP")
datalink_cleanup();
}
res |= close;
server_node.init_state = 0;
/* bacnet library close */
// Nothing to do ???
return res;
}