bacnet/runtime/bi.c
author Edouard Tisserant <edouard.tisserant@gmail.com>
Thu, 10 Dec 2020 11:37:27 +0100
changeset 2697 93333d206198
parent 2020 6dddf3070806
permissions -rw-r--r--
Python Safe Globals now have more reliable triggering of OnChange call. Added "Onchange" object to accessible runtime variables that let user python code see count of changes and first and last values.
/**************************************************************************
*
* Copyright (C) 2006 Steve Karg <skarg@users.sourceforge.net>
* Copyright (C) 2017 Mario de Sousa <msousa@fe.up.pt>
*
* Permission is hereby granted, free of charge, to any person obtaining
* a copy of this software and associated documentation files (the
* "Software"), to deal in the Software without restriction, including
* without limitation the rights to use, copy, modify, merge, publish,
* distribute, sublicense, and/or sell copies of the Software, and to
* permit persons to whom the Software is furnished to do so, subject to
* the following conditions:
*
* The above copyright notice and this permission notice shall be included
* in all copies or substantial portions of the Software.
*
* THE SOFTWARE IS PROVIDED "AS IS", WITHOUT WARRANTY OF ANY KIND,
* EXPRESS OR IMPLIED, INCLUDING BUT NOT LIMITED TO THE WARRANTIES OF
* MERCHANTABILITY, FITNESS FOR A PARTICULAR PURPOSE AND NONINFRINGEMENT.
* IN NO EVENT SHALL THE AUTHORS OR COPYRIGHT HOLDERS BE LIABLE FOR ANY
* CLAIM, DAMAGES OR OTHER LIABILITY, WHETHER IN AN ACTION OF CONTRACT,
* TORT OR OTHERWISE, ARISING FROM, OUT OF OR IN CONNECTION WITH THE
* SOFTWARE OR THE USE OR OTHER DEALINGS IN THE SOFTWARE.
*
*********************************************************************/

/* Binary Input Objects - customize for your use */

#include <stdbool.h>
#include <stdint.h>
#include <stdio.h>

#include "config_bacnet_for_beremiz_%(locstr)s.h"     /* the custom configuration for beremiz plugin */
#include "bacdef.h"
#include "bacdcode.h"
#include "bacenum.h"
#include "bacapp.h"
#include "wp.h"
#include "rp.h"
#include "bi_%(locstr)s.h"
#include "handlers.h"



/* initial value for present_value property of each object */ 
#define BI_VALUE_INIT (0)


/* The IEC 61131-3 located variables mapped onto the Binary Input objects of BACnet protocol */
%(BI_lvars)s


/* The array where we keep all the state related to the Binary Input Objects */
#define MAX_BINARY_INPUTS %(BI_count)s
static BINARY_INPUT_DESCR BI_Descr[MAX_BINARY_INPUTS] = {
%(BI_param)s
};




/* These three arrays are used by the ReadPropertyMultiple handler,
 * as well as to initialize the XXX_Property_List used by the 
 * Property List (PROP_PROPERTY_LIST) property.
 */
static const int Binary_Input_Properties_Required[] = {
 /* (1) Currently Supported                  */
 /* (2) Required by standard ASHRAE 135-2016 */
                              /*(1)(2)      */
    PROP_OBJECT_IDENTIFIER,   /* R  R ( 75) */
    PROP_OBJECT_NAME,         /* R  R ( 77) */
    PROP_OBJECT_TYPE,         /* R  R ( 79) */
    PROP_PRESENT_VALUE,       /* W  R ( 85) */
    PROP_STATUS_FLAGS,        /* R  R (111) */
    PROP_EVENT_STATE,         /* R  R ( 36) */
    PROP_OUT_OF_SERVICE,      /* W  R ( 81) */
    PROP_POLARITY,            /* R  R ( 84) */
//  PROP_PROPERTY_LIST,       /* R  R (371) */
    -1
};

static const int Binary_Input_Properties_Optional[] = {
 /* (1) Currently Supported                  */
 /* (2) Required by standard ASHRAE 135-2016 */
                              /*(1)(2)      */
    PROP_DESCRIPTION,         /* R  O ( 28) */
    -1
};

static const int Binary_Input_Properties_Proprietary[] = {
    -1
};


/* This array stores the PROPERTY_LIST which may be read by clients.
 * End of list is marked by following the last element with the value '-1'
 * 
 * It is initialized by Binary_Input_Init() based off the values
 * stored in Binary_Input_Properties_Required 
 *           Binary_Input_Properties_Optional
 *           Binary_Input_Properties_Proprietary
 */
/* TODO: Allocate memory for this array with malloc() at startup */
static int Binary_Input_Properties_List[64];





/********************************************************/
/**                  Callback functions.               **/
/** Functions required by BACnet devie implementation. **/
/********************************************************/


/* This is a callback function. Callback set in My_Object_Table[] array declared in device.c,  */
void Binary_Input_Property_Lists(
    const int **pRequired,
    const int **pOptional,
    const int **pProprietary)
{
    if (pRequired)
        *pRequired = Binary_Input_Properties_Required;
    if (pOptional)
        *pOptional = Binary_Input_Properties_Optional;
    if (pProprietary)
        *pProprietary = Binary_Input_Properties_Proprietary;

    return;
}


/* This is a callback function. Callback set in My_Object_Table[] array declared in device.c,  */
void Binary_Input_Init(
    void)
{
    unsigned i, j;
    static bool initialized = false;

    // fprintf(stderr, "BACnet plugin: Binary_Input_Init() called!\n");
    
    if (!initialized) {
        initialized = true;

        /* initialize the Binary_Input_Properties_List array */
        int len = 0;
        len += BACnet_Init_Properties_List(Binary_Input_Properties_List + len,
                                           Binary_Input_Properties_Required);
        len += BACnet_Init_Properties_List(Binary_Input_Properties_List + len,
                                           Binary_Input_Properties_Optional);
        len += BACnet_Init_Properties_List(Binary_Input_Properties_List + len,
                                           Binary_Input_Properties_Proprietary);

        /* initialize all the binary values priority arrays to NULL */
        for (i = 0; i < MAX_BINARY_INPUTS; i++) {
            BI_Descr[i].Present_Value = BI_VALUE_INIT;
            BI_Descr[i].Polarity      = POLARITY_NORMAL;
        }
    }

    return;
}



/* validate that the given instance (Object ID) exists */
/* This is a callback function. Callback set in My_Object_Table[] array declared in device.c,  */
bool Binary_Input_Valid_Instance(
    uint32_t object_instance)
{
    // fprintf(stderr, "BACnet plugin: Binary_Input_Valid_Instance(obj_ID=%%u) called!\n", object _instance);
    return (Binary_Input_Instance_To_Index(object_instance) < MAX_BINARY_INPUTS);
}


/* the number of Binary Input Objects */
/* This is a callback function. Callback set in My_Object_Table[] array declared in device.c,  */
unsigned Binary_Input_Count(void)   {return MAX_BINARY_INPUTS;}


/* returns the instance (i.e. Object Identifier) that correlates to the correct index */
/* This is a callback function. Callback set in My_Object_Table[] array declared in device.c,  */
uint32_t Binary_Input_Index_To_Instance(unsigned index) {return BI_Descr[index].Object_Identifier;}


/* returns the index that correlates to the correct instance number (Object Identifier) */
unsigned Binary_Input_Instance_To_Index(
    uint32_t object_instance)
{
    unsigned index = 0;
  
    for (index = 0; index < MAX_BINARY_INPUTS; index++)
        if (object_instance == BI_Descr[index].Object_Identifier)
            return index;

    /* error, this object ID is not in our list! */
    return MAX_BINARY_INPUTS;
}



BACNET_BINARY_PV Binary_Input_Present_Value(
    uint32_t object_instance)
{
    BACNET_BINARY_PV value = BI_VALUE_INIT;
    unsigned index = 0;
    unsigned i = 0;

    // fprintf(stderr, "BACnet plugin: Binary_Input_Present_Value(obj_ID=%%u) called!\n", object_instance);

    index = Binary_Input_Instance_To_Index(object_instance);
    if (index < MAX_BINARY_INPUTS)
        value = BI_Descr[index].Present_Value;

    return value;
}



/* note: the object name must be unique within this device */
/* This is a callback function. Callback set in My_Object_Table[] array declared in device.c,  */
bool Binary_Input_Object_Name(
    uint32_t object_instance,
    BACNET_CHARACTER_STRING * object_name)
{
    bool    status = false;
    unsigned index = Binary_Input_Instance_To_Index(object_instance);

    if (index < MAX_BINARY_INPUTS)
        status = characterstring_init_ansi(object_name, BI_Descr[index].Object_Name);
    
    return status;
}



bool Binary_Input_Object_Description(
    uint32_t object_instance,
    BACNET_CHARACTER_STRING * object_name)
{
    bool    status = false;
    unsigned index = Binary_Input_Instance_To_Index(object_instance);

    if (index < MAX_BINARY_INPUTS)
        status = characterstring_init_ansi(object_name, BI_Descr[index].Description);
    
    return status;    
}



/* return apdu len, or BACNET_STATUS_ERROR on error */
/* This is a callback function. Callback set in My_Object_Table[] array declared in device.c,  */
int Binary_Input_Read_Property(
    BACNET_READ_PROPERTY_DATA * rpdata)
{
    int len = 0;
    int apdu_len = 0;   /* return value */
    BACNET_BIT_STRING bit_string;
    BACNET_CHARACTER_STRING char_string;
    BACNET_BINARY_PV present_value = BINARY_INACTIVE;
    unsigned object_index = 0;
    unsigned i = 0;
    bool state = false;
    uint8_t *apdu = NULL;

    // fprintf(stderr, "BACnet plugin: Binary_Input_Read_Property() called!\n");

    if ((rpdata == NULL) || (rpdata->application_data == NULL) ||
        (rpdata->application_data_len == 0)) {
        return 0;
    }
    
    object_index = Binary_Input_Instance_To_Index(rpdata->object_instance);
    if (object_index >= MAX_BINARY_INPUTS) {
        rpdata->error_class = ERROR_CLASS_OBJECT;
        rpdata->error_code  = ERROR_CODE_UNKNOWN_OBJECT;
        return BACNET_STATUS_ERROR;
    }
    
    apdu = rpdata->application_data;
    switch (rpdata->object_property) {
        case PROP_OBJECT_IDENTIFIER:
            apdu_len =
                encode_application_object_id(&apdu[0], OBJECT_BINARY_INPUT,
                rpdata->object_instance);
            break;
        case PROP_OBJECT_NAME:
            Binary_Input_Object_Name(rpdata->object_instance, &char_string);
            apdu_len =
                encode_application_character_string(&apdu[0], &char_string);
            break;
        case PROP_DESCRIPTION:
            Binary_Input_Object_Description(rpdata->object_instance, &char_string);
            apdu_len =
                encode_application_character_string(&apdu[0], &char_string);
            break;
        case PROP_OBJECT_TYPE:
            apdu_len =
                encode_application_enumerated(&apdu[0], OBJECT_BINARY_INPUT);
            break;
        case PROP_PRESENT_VALUE:
            present_value =
                Binary_Input_Present_Value(rpdata->object_instance);
            apdu_len = encode_application_enumerated(&apdu[0], present_value);
            break;
        case PROP_STATUS_FLAGS:
            /* note: see the details in the standard on how to use these */
            bitstring_init(&bit_string);
            bitstring_set_bit(&bit_string, STATUS_FLAG_IN_ALARM, false);
            bitstring_set_bit(&bit_string, STATUS_FLAG_FAULT, false);
            bitstring_set_bit(&bit_string, STATUS_FLAG_OVERRIDDEN, false);
            state = BI_Descr[object_index].Out_Of_Service;
            bitstring_set_bit(&bit_string, STATUS_FLAG_OUT_OF_SERVICE, state);
            apdu_len = encode_application_bitstring(&apdu[0], &bit_string);
            break;
        case PROP_EVENT_STATE:
            /* note: see the details in the standard on how to use this */
            apdu_len =
                encode_application_enumerated(&apdu[0], EVENT_STATE_NORMAL);
            break;
        case PROP_OUT_OF_SERVICE:
            state = BI_Descr[object_index].Out_Of_Service;
            apdu_len = encode_application_boolean(&apdu[0], state);
            break;
        case PROP_POLARITY:
            apdu_len = encode_application_enumerated(&apdu[0],
                                BI_Descr[object_index].Polarity);
            break;
//      case PROP_PROPERTY_LIST:
//          BACnet_encode_array(Binary_Input_Properties_List,
//                              property_list_count(Binary_Input_Properties_List),
//                              retfalse, encode_application_enumerated);
//          break;
        default:
            rpdata->error_class = ERROR_CLASS_PROPERTY;
            rpdata->error_code  = ERROR_CODE_UNKNOWN_PROPERTY;
            apdu_len = BACNET_STATUS_ERROR;
            break;
    }
    /*  only array properties can have array options */
    if ((apdu_len >= 0) &&
//      (rpdata->object_property != PROP_PROPERTY_LIST) &&
        (rpdata->array_index != BACNET_ARRAY_ALL)) {
        rpdata->error_class = ERROR_CLASS_PROPERTY;
        rpdata->error_code = ERROR_CODE_PROPERTY_IS_NOT_AN_ARRAY;
        apdu_len = BACNET_STATUS_ERROR;
    }

    return apdu_len;
}




/* returns true if successful */
/* This is a callback function. Callback set in My_Object_Table[] array declared in device.c,  */
bool Binary_Input_Write_Property(
    BACNET_WRITE_PROPERTY_DATA * wp_data)
{
    bool status = false;        /* return value */
    unsigned int object_index = 0;
    unsigned int priority = 0;
    BACNET_BINARY_PV level = BINARY_NULL;
    int len = 0;
    BACNET_APPLICATION_DATA_VALUE value;

    /* decode the some of the request */
    len =
        bacapp_decode_application_data(wp_data->application_data,
        wp_data->application_data_len, &value);
    /* FIXME: len < application_data_len: more data? */
    if (len < 0) {
        /* error while decoding - a value larger than we can handle */
        wp_data->error_class = ERROR_CLASS_PROPERTY;
        wp_data->error_code = ERROR_CODE_VALUE_OUT_OF_RANGE;
        return false;
    }
    /*  only array properties can have array options */
    if (wp_data->array_index != BACNET_ARRAY_ALL) {
        wp_data->error_class = ERROR_CLASS_PROPERTY;
        wp_data->error_code = ERROR_CODE_PROPERTY_IS_NOT_AN_ARRAY;
        return false;
    }
    /* No need to check whether object_index is within bounds.
     * Has already been checked before Binary_Input_Write_Property() is called
     */
    object_index = Binary_Input_Instance_To_Index(wp_data->object_instance);
    
    switch (wp_data->object_property) {
        case PROP_PRESENT_VALUE:
            status =
                WPValidateArgType(&value, BACNET_APPLICATION_TAG_ENUMERATED,
                &wp_data->error_class, &wp_data->error_code);
            if (!status) {
                wp_data->error_class = ERROR_CLASS_PROPERTY;
                wp_data->error_code  = ERROR_CODE_VALUE_OUT_OF_RANGE;
            } else {
                if (!BI_Descr[object_index].Out_Of_Service) {
                    /* input objects can only be written to when Out_Of_Service is true! */
                    wp_data->error_class = ERROR_CLASS_PROPERTY;
                    wp_data->error_code  = ERROR_CODE_WRITE_ACCESS_DENIED;
                    status = false; // not really necessary here.
                } else {
                    if (!(value.type.Enumerated <= MAX_BINARY_PV)) {
                        wp_data->error_class = ERROR_CLASS_PROPERTY;
                        wp_data->error_code  = ERROR_CODE_VALUE_OUT_OF_RANGE;
                        status = false;
                    } else {
                        level = (BACNET_BINARY_PV) value.type.Enumerated;
                        BI_Descr[object_index].Present_Value = level;
                        status = true;
                    }
                }
            }
            break;
        case PROP_OUT_OF_SERVICE:
        {
            bool Previous_Out_Of_Service = BI_Descr[object_index].Out_Of_Service;
            status =
                WPValidateArgType(&value, BACNET_APPLICATION_TAG_BOOLEAN,
                &wp_data->error_class, &wp_data->error_code);
            if (status) {
                BI_Descr[object_index].Out_Of_Service = value.type.Boolean;
                if (Previous_Out_Of_Service && !BI_Descr[object_index].Out_Of_Service)
                    /* We have just changed from Out_of_Service -> In Service */
                    /* We need to update the Present_Value to the value
                     * currently in the PLC...
                     */
                    BI_Descr[object_index].Present_Value =
                                           *(BI_Descr[object_index].Located_Var_ptr);
            }
            break;
        }
        case PROP_OBJECT_IDENTIFIER:
        case PROP_OBJECT_NAME:
        case PROP_DESCRIPTION:
        case PROP_OBJECT_TYPE:
        case PROP_STATUS_FLAGS:
        case PROP_EVENT_STATE:
        case PROP_POLARITY:
//      case PROP_PROPERTY_LIST:
            wp_data->error_class = ERROR_CLASS_PROPERTY;
            wp_data->error_code = ERROR_CODE_WRITE_ACCESS_DENIED;
            break;
        default:
            wp_data->error_class = ERROR_CLASS_PROPERTY;
            wp_data->error_code = ERROR_CODE_UNKNOWN_PROPERTY;
            break;
    }

    return status;
}





/********************************************/
/** Functions required for Beremiz plugin  **/
/********************************************/



void  Binary_Input_Copy_Present_Value_to_Located_Var(void) {
    unsigned i;
    for (i = 0; i < MAX_BINARY_INPUTS; i++) {
        // decouple PLC's Located Variable from Bacnet Object's Present Value if Out_Of_Service is true
        if (BI_Descr[i].Out_Of_Service)
            continue;

        // copy the value
        *(BI_Descr[i].Located_Var_ptr) = Binary_Input_Present_Value(BI_Descr[i].Object_Identifier);
    }
}
  
void  Binary_Input_Copy_Located_Var_to_Present_Value(void) {
    unsigned i;
    for (i = 0; i < MAX_BINARY_INPUTS; i++) {
        // decouple PLC's Located Variable from Bacnet Object's Present Value if Out_Of_Service is true
        if (BI_Descr[i].Out_Of_Service)
            continue;

        // copy the value (0 is false, all other values are true)
        if (*(BI_Descr[i].Located_Var_ptr))
            BI_Descr[i].Present_Value = BINARY_ACTIVE;
        else
            BI_Descr[i].Present_Value = BINARY_INACTIVE;
    }
}