Edouard Tisserant [Wed, 01 Jul 2020 10:36:20 +0200] rev 2686
Modbus and Bacnet websettings : Rename variables and functions to avoid name collisions.
Websettings for modbus and bacnet are now passed to runtime as python files loaded (execfile) at init of PLCObject with the same globals.
Because if this, same names used in previously different modules now colide.
Edouard Tisserant [Mon, 29 Jun 2020 14:38:04 +0200] rev 2685
Modbus: fix strange side effect of re-use of condition variables or mutex with Xenomai : without bzero of the associated types, mutex keeps locked.
Edouard Tisserant [Wed, 24 Jun 2020 14:38:11 +0200] rev 2684
Modbus: fix client timer invalid arguments.