Variable forcing now uses limited list and buffer instead of systematical instance tree traversal and in-tree "fvalue" to keep track of forced value for pointed variables (external, located). Pointer swapping is performed when forcing externals and located, with backup being restored when forcing is reset. Match Beremiz commit 93ad018fb602.
(* Following taken directly from the IEC 61131.3 draft standard *)
(*
* An IEC 61131-3 IL and ST compiler.
*
* Based on the
* FINAL DRAFT - IEC 61131-3, 2nd Ed. (2001-12-10)
*
*)
FUNCTION_BLOCK RAMP
VAR_INPUT
RUN : BOOL ; (* 0 - track X0, 1 - ramp to/track X1 *)
X0,X1 : REAL ;
TR : TIME ; (* Ramp duration *)
CYCLE : TIME ; (* Sampling period *)
END_VAR
VAR_OUTPUT
BUSY : BOOL ; (* BUSY = 1 during ramping period *)
XOUT : REAL := 0.0 ;
END_VAR
VAR XI : REAL ; (* Initial value *)
T : TIME := T#0s; (* Elapsed time of ramp *)
END_VAR
BUSY := RUN ;
IF RUN THEN
IF T >= TR THEN BUSY := 0 ; XOUT := X1 ;
ELSE XOUT := XI + (X1-XI) * TIME_TO_REAL(T)
/ TIME_TO_REAL(TR) ;
T := T + CYCLE ;
END_IF ;
ELSE XOUT := X0 ; XI := X0 ; T := t#0s ;
END_IF ;