Dominik Staubli <ch1010252@ch10pc423> [Thu, 21 Jan 2010 11:09:31 +0100] rev 1798
Domain datagram working counter calculation bugfix: increment expected wc for a given slave & direction just once for each datagram
This bug occurs if you configure more than one SM in the same direction on the same slave